Skip to product information
1 of 8

PayPal, credit cards. Download editable-PDF and invoice in 1 second!

GB/T 17626.5-2008 English PDF (GBT17626.5-2008)

GB/T 17626.5-2008 English PDF (GBT17626.5-2008)

Regular price $140.00 USD
Regular price Sale price $140.00 USD
Sale Sold out
Shipping calculated at checkout.
Delivery: 3 seconds. Download true-PDF + Invoice.Newer version: (Replacing this standard) GB/T 17626.5-2019
Get QUOTATION in 1-minute: Click GB/T 17626.5-2008
Historical versions: GB/T 17626.5-2008
Preview True-PDF (Reload/Scroll if blank)

GB/T 17626.5-2008: Electromagnetic compatibility -- Testing and measurement techniques -- Surge immunity test
GB/T 17626.5-2008
ICS 33.100
L 06
GB
National Standard
of The People’s Republic of China
GB/T 17626.5-2008/IEC 61000-4-5.2005
Replacing GB/T 17626.5-1999
Electromagnetic compatibility –
Testing and measurement techniques –
Surge immunity test
(IEC 61000-4-5.2005, IDT)
ISSUED ON. MAY 20, 2008
IMPLEMENTED ON. JANUARY 1, 2009
Issued by. The General Administration of Quality Supervision, Inspection and Quarantine
of PRC; and China National Standardization Administration Committee
Table of Contents
Preface ... 3
1 Scope ... 7
2 Normative references ... 8
3 Terms and definitions ... 8
4 General ... 14
5 Test levels ... 15
6 Test instrumentation ... 16
7 Test setup ... 35
8 Test procedure ... 40
9 Evaluation of test results ... 41
10 Test report ... 42
Annex A (informative) Selection of generators and test levels ... 43
Annex B (informative) Explanatory notes... 45
B.1 Different source Impedance ... 45
B.2 Application of the tests ... 45
B.3 Installation classification ... 46
B.4 Minimum immunity level of ports connected to the power supply network ... 48
B.5 Equipment level immunity of ports connected to interconnection lines ... 48
Annex C (informative) Considerations for achieving immunity for equipment
connected to low voltage power systems ... 49
References ... 51
Preface
GB/T 17626 EMC Testing and Measurement Techniques currently includes the following
components.
GB/T 17626.1-2006 Electromagnetic compatibility Testing and measurement techniques
Overview of immunity tests
GB/T 17626.2-2006 Electromagnetic compatibility Testing and measurement techniques
Electrostatic discharge immunity test
GB/T 17626.3-2006 Electromagnetic compatibility Testing and measurement techniques
Radiated, radio-frequency, Electromagnetic field immunity test
GB/T 17626.4-2006 Electromagnetic compatibility Testing and measurement techniques
Electrical fast transient/burst immunity test
GB/T 17626.5-2006 Electromagnetic compatibility Testing and measurement techniques
Surge immunity test
GB/T 17626.6-2006 Electromagnetic compatibility Testing and measurement techniques
Immunity to conducted disturbance, induced by radio-frequency fields
GB/T 17626.7-2006 Electromagnetic compatibility Testing and measurement techniques -
General guide on harmonics and interharmonics measurements and instrumentation, for
power supply systems and equipment connected thereto
GB/T 17626.8-1998 Electromagnetic compatibility Testing and measurement techniques
Power frequency magnetic field immunity test
GB/T 17626.9-2006 Electromagnetic compatibility Testing and measurement techniques
- Pulse magnetic field immunity test
GB/T 17626.10-2006 Electromagnetic compatibility Testing and measurement techniques
- Damped oscillatory magnetic field immunity test
GB/T 17626.11-2006 Electromagnetic compatibility Testing and measurement techniques
Voltage dips, short interruptions and voltage variations immunity test
GB/T 17626.12-2006 Electromagnetic compatibility Testing and measurement techniques
- Oscillatory waves immunity test
GB/T 17626.13-2006 Electromagnetic compatibility Testing and measurement techniques
- Harmonics and interharmonics including mains signaling at a.c. power port, low frequency
immunity test
GB/T 17626.14-2006 Electromagnetic compatibility Testing and measurement techniques
- Voltage fluctuation immunity test
GB/T 17626.16-2006 Electromagnetic compatibility Testing and measurement techniques
- Test for immunity to conducted, common mode disturbances in the frequency range 0 Hz to
150 kHz
GB/T 17626.17-2006 Electromagnetic compatibility Testing and measurement techniques
- Ripple on d.c. input power port immunity test
GB/T 17626.27-2006 Electromagnetic compatibility Testing and measurement techniques
- Unbalance immunity test
GB/T 17626.28-2006 Electromagnetic compatibility Testing and measurement techniques -
Variation of power frequency, immunity test
GB/T 17626.29-2006 Electromagnetic compatibility Testing and Measurement Techniques.
Voltage Dips, Short Interruptions and Voltage Variations on DC Input Port Immunity Test
This Standard is the Part 5 of GB/T 17626.
This Standard is equivalent to IEC 61000-4-5.2005 (Ed. 2) Electromagnetic compatibility
Testing and measurement techniques Surge immunity test
In this Part, the vertical axis title of figure 2, 3, 5 and 6 in IEC 61000-4-5.2005 are modified.
This Part replaces GB/T 17626.5- 1999 Electromagnetic compatibility Testing and
measurement techniques Surge immunity test
Some contents in this document may involve the patents. The publisher of this document does
not assume responsibility for identifying these patents.
This Standard has the following main difference from GB/T 17626.5-1999.
1) Add new definitions
2) Add 10/700μs open-circuit voltage wave shape and 5/320μs short-circuit current wave
shape;
3) Define the voltage/current waveform at EUT port in coupling/decoupling network;
4) Add coupling/decoupling network selection procedure diagram;
5) In the configuration of unshielded unsymmetrical interconnection lines, add coupling via
a clamping circuit.
6) In the configuration of unshielded unsymmetrical interconnection lines, delete
“Line-to-ground coupling”, and only define “all line-to-ground” coupling, and also
change the coupling method to via arrestor.
7) Add the test requirements for high speed communications lines
8) Cancel the requirement for earth connection capacitor for the test of shielded lines
grounded only at one end;
9) Add Alternative coupling method for testing single cables in a multi-shield configuration
10) Change the surge Repetition rate to at least 1/ minute.
11) Modify 8.1.1 Climatic conditions
12) Modify Evaluation of test results
13) Define the specific requirements for test report;
14) Modify Table A.1 Selection of the test levels
15) Add the description of system level immunity in Annex B, and delete figure B.1 through
Figure B.3 in 1999 version.
16) Add Annex C.
17) Re-edit the content of this Standard.
a) Exchange Clause 4 Definition with Clause 3 “General”;
b) Change the centralized figure arrangement in the original standard into distributed
arrangement by distributing the figures into the corresponding text.
Annex A, B, and C of this Standard are informative annex.
The specification is proposed and managed by China National EMC Standardization
Technical Committee (SAC/TC 246).
This Standard is drafted by. China MII Electronics Industry Standardization Institute.
This Standard is written by. CHEN Shigang, Liu Jianpeng, Cai Hua-Qiang.
This Standard replaces all the previous releases.
- GB/T 17626.5-1999.
Electromagnetic compatibility
- Testing and measurement techniques
- Surge immunity test
1 Scope
This Part of GB/T 17626 relates to the immunity requirements, test methods, and range of
recommended test levels for equipment to unidirectional surges caused by overvoltage from
switching and lightning transients. Several test levels which relate to different environment
and installation conditions are defined. These requirements are developed for and are
applicable to electrical and electronic equipment.
The objective of this Standard is to establish a common reference for evaluating the immunity
of electrical and electronic equipment when subjected to surges. The test method documented
in this Part describes a consistent method to assess th...