GB/T 8801-2007: Test method for unplasticized polyvinyl chloride (PVC-U) fittings by falling
GB/T 8801-2007
NATIONAL STANDARD OF THE
PEOPLE’S REPUBLIC OF CHINA
ICS 83.140.30
G 33
Replacing GB/T 8801-1988
Test method for unplasticized polyvinyl chloride
(PVC-U) fittings by falling
ISSUED ON: DECEMBER 05, 2007
IMPLEMENTED ON: SEPTEMBER 01, 2008
Issued by: General Administration of Quality Supervision, Inspection and
Quarantine;
Standardization Administration of the People’s Republic of
China.
Table of Contents
Foreword ... 3
1 Scope ... 4
2 Principle ... 4
3 Instruments and apparatuses ... 4
4 Test sample and its preparation... 4
5 Test conditions ... 4
6 Test steps ... 5
7 Result judgment ... 5
8 Test report ... 6
Foreword
This Standard closely combines domestic plastic product developments, and
refers to technical contents of relevant domestic standards, to amend GB/T
8801-1988 "Test method for unplasticized PVC fittings by falling".
This Standard replaces GB/T 8801-1988 "Test method for unplasticized PVC
fittings by falling". Compared with the latter, the main change is the division of
the requirements for the falling height:
-- Fittings, whose nominal diameter is less than or equal to 75 mm, fall from
(2.00 ± 0.05) m above the ground;
-- Fittings, whose nominal diameter is greater than 75 mm and less than 200
mm, fall from (1.00 ± 0.05) m above the ground;
-- Fittings, whose nominal diameter is equal to or greater than 200 mm, fall
from (0.50 ± 0.05) m above the ground.
This Standard was proposed by China National Light Industry Council.
This Standard shall be under the jurisdiction of Sub-Committee of Plastics Pipe,
Fitting and Valves, Committee of National Standardization for Plastics Products
(SAC/C 48/SC 3).
The drafting organizations of this Standard: Wuzhou Wuyi Plastic Product Co.,
Ltd., Sichuan Chuanke Plastic Cement Group.
The drafters of this Standard: Huang Wanxia, Jiao Dachuan.
The previous version of the standard which is replaced by this Standard is:
-- GB/T 8801-1988.
Test method for unplasticized polyvinyl chloride
(PVC-U) fittings by falling
1 Scope
This Standard specifies the test method for unplasticized polyvinyl chloride
(PVC-U) fittings by falling.
This Standard applies to various uses of unplasticized polyvinyl chloride (PVC-
U) fittings.
2 Principle
In this method, pretreat the fitting at (0 ± 1) °C for a prescribed period of time;
let it freely fall from a prescribed height to a flat concrete floor within 10 s;
observe the damage of the fitting.
3 Instruments and apparatuses
3.1 Stopwatch: the division value is 0.1 s.
3.2 Thermometer: the division value is 1 °C.
3.3 Constant-temperature water bath (ice water mixture inside) or cryogenic
box: the temperature is (0 ± 1) °C.
4 Test sample and its preparation
4.1 The test sample is a complete fitting of injection molding. If the fitting is
equipped with an elastic seal, it shall be removed before testing. If the fitting
consists of more than one injection-molded parts, these parts shall be tested
separately from each other.
4.2 The number of test samples shall be in accordance with the product
standards. For the same batch of products of the same specification, at least
take 5 test samples. The test samples shall be free of mechanical damage.
5 Test conditions
5.1 Falling height
Get QUOTATION in 1-minute: Click GB/T 8801-2007
Historical versions: GB/T 8801-2007
Preview True-PDF (Reload/Scroll if blank)
GB/T 8801-2007: Test method for unplasticized polyvinyl chloride (PVC-U) fittings by falling
GB/T 8801-2007
NATIONAL STANDARD OF THE
PEOPLE’S REPUBLIC OF CHINA
ICS 83.140.30
G 33
Replacing GB/T 8801-1988
Test method for unplasticized polyvinyl chloride
(PVC-U) fittings by falling
ISSUED ON: DECEMBER 05, 2007
IMPLEMENTED ON: SEPTEMBER 01, 2008
Issued by: General Administration of Quality Supervision, Inspection and
Quarantine;
Standardization Administration of the People’s Republic of
China.
Table of Contents
Foreword ... 3
1 Scope ... 4
2 Principle ... 4
3 Instruments and apparatuses ... 4
4 Test sample and its preparation... 4
5 Test conditions ... 4
6 Test steps ... 5
7 Result judgment ... 5
8 Test report ... 6
Foreword
This Standard closely combines domestic plastic product developments, and
refers to technical contents of relevant domestic standards, to amend GB/T
8801-1988 "Test method for unplasticized PVC fittings by falling".
This Standard replaces GB/T 8801-1988 "Test method for unplasticized PVC
fittings by falling". Compared with the latter, the main change is the division of
the requirements for the falling height:
-- Fittings, whose nominal diameter is less than or equal to 75 mm, fall from
(2.00 ± 0.05) m above the ground;
-- Fittings, whose nominal diameter is greater than 75 mm and less than 200
mm, fall from (1.00 ± 0.05) m above the ground;
-- Fittings, whose nominal diameter is equal to or greater than 200 mm, fall
from (0.50 ± 0.05) m above the ground.
This Standard was proposed by China National Light Industry Council.
This Standard shall be under the jurisdiction of Sub-Committee of Plastics Pipe,
Fitting and Valves, Committee of National Standardization for Plastics Products
(SAC/C 48/SC 3).
The drafting organizations of this Standard: Wuzhou Wuyi Plastic Product Co.,
Ltd., Sichuan Chuanke Plastic Cement Group.
The drafters of this Standard: Huang Wanxia, Jiao Dachuan.
The previous version of the standard which is replaced by this Standard is:
-- GB/T 8801-1988.
Test method for unplasticized polyvinyl chloride
(PVC-U) fittings by falling
1 Scope
This Standard specifies the test method for unplasticized polyvinyl chloride
(PVC-U) fittings by falling.
This Standard applies to various uses of unplasticized polyvinyl chloride (PVC-
U) fittings.
2 Principle
In this method, pretreat the fitting at (0 ± 1) °C for a prescribed period of time;
let it freely fall from a prescribed height to a flat concrete floor within 10 s;
observe the damage of the fitting.
3 Instruments and apparatuses
3.1 Stopwatch: the division value is 0.1 s.
3.2 Thermometer: the division value is 1 °C.
3.3 Constant-temperature water bath (ice water mixture inside) or cryogenic
box: the temperature is (0 ± 1) °C.
4 Test sample and its preparation
4.1 The test sample is a complete fitting of injection molding. If the fitting is
equipped with an elastic seal, it shall be removed before testing. If the fitting
consists of more than one injection-molded parts, these parts shall be tested
separately from each other.
4.2 The number of test samples shall be in accordance with the product
standards. For the same batch of products of the same specification, at least
take 5 test samples. The test samples shall be free of mechanical damage.
5 Test conditions
5.1 Falling height