Preview True-PDF (Reload/Scroll if blank)
GB 40881-2021: Code for security system design of low concentration gas pipeline transportation of coal mine
GB 40881-2021
GB
NATIONAL STANDARD OF THE
PEOPLE’S REPUBLIC OF CHINA
ICS 13.100
CCS D 09
Code for security system design of low concentration gas
pipeline transportation of coal mine
ISSUED ON: OCTOBER 11, 2021
IMPLEMENTED ON: MAY 01, 2022
Issued by: State Administration for Market Regulation;
Standardization Administration of the People's Republic of China.
Table of Contents
Foreword ... 3
Introduction ... 4
1 Scope ... 6
2 Normative references ... 6
3 Terms and definitions ... 7
4 Basic requirements ... 8
5 Security facilities ... 9
6 Others ... 12
Code for security system design of low concentration gas
pipeline transportation of coal mine
1 Scope
This document specifies the basic requirements for the design of the security system for
low concentration gas pipeline transportation of coal mine, the installation requirements
for security facilities.
This document is applicable to the security system design of low concentration gas
pipeline transportation of coal mine.
2 Normative references
The following referenced documents are indispensable for the application of this
document. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
GB 50016, Code for Fire Protection Design of Buildings
GB 50028, Code for design of city gas engineering
GB 50057, Code for design protection of structures against lightning
GB 50471, Code for design of the gas drainage engineering of coal mine
AQ 1072, Specification for water sealing of fire barriering and explosion venting
devices of gas pipeline transportation
AQ 1073, Specification for automatic preventing explosion devices of gas piping
AQ 1078, General specifications for transmission system of low concentration coal
mine gas blending with water mist
AQ 1079, General specification for automatic spurting powder explosion
suppression devices of gas pipeline transmission
AQ/T 1104, Technical Rules for the Security Delivery Device of Gas-water Two-
phase Flow of Low Concentration Gas in Coal Mine
CJJ 33, Code for construction and acceptance of city and town gas distribution
works
A device that the continuous mixing of gas and fine water mist in the coal mine gas
pipeline can inhibit the flame propagation of combustion or explosion.
4 Basic requirements
4.1 In the low concentration gas pipeline transportation of coal mine, close to the
possible fire source points (generator set intake side, ground emptying nozzle,
spontaneous combustion and easy spontaneous combustion coal seam gob drainage gas
pipe inlet), a security system shall be installed to ensure the security of pipeline
transportation.
4.2 The system design shall follow the basic principles of "fire and explosion prevention,
explosion suppression and explosion prevention, multi-level protection, and security
assurance". The security system shall choose different combinations of security
facilities such as fire and explosion relief, explosion suppression, explosion prevention,
anti-backflow, security monitoring and control, and lightning protection according to
the different uses of gas transportation.
4.3 Anti-backflow devices shall be installed in the positive pressure pipeline system.
Prevent backflow due to sudden shutdown of the extraction pump.
4.4 Buffer tanks shall not be installed in low concentration gas pipeline transportation
systems.
4.5 Pressurization equipment shall choose a wet compressor.
4.6 Drainage equipment shall choose wet drainage pumps.
4.7 When conveying under positive pressure, the conveying pressure shall not exceed
20kPa.
4.8 There shall be no mechanical moving parts and electrical components in the
dehydrator.
4.9 Security monitoring and control facilities shall be set up in the pipeline
transportation system. In addition to complying with the relevant provisions of MT209,
security monitoring and control facilities shall also have the following functions:
a) The function of state parameter monitoring and alarm of gas pipeline
transportation security facilities;
b) In the event of gas combustion or explosion, it shall be possible to control the
rapid start-up of security equipment. Control gas combustion or explosion within a
certain range.
4.10 The pipelines and accessories in the security facility installation section shall be
6 - Water sealing of fire barriering and explosion venting device;
7 - Pressure sensor;
8 - Flame sensor;
9 - Power equipment;
10 - Branch pipe;
11 - Airflow direction.
Figure 1 -- Schematic diagram of installation of security facilities for gas power
generation utilization system
5.1.3 Flame and pressure sensors for monitoring are installed on the branch pipe. The
flame sensor is no more than 3m away from the generator set. The pressure sensor is
3m~5m away from the flame sensor. If a dehydrator is installed on the branch pipe, the
flame sensor is located between the dehydrator and the generator set, 2m~3m away
from the dehydrator. The pressure sensor is located between the dehydrator and the
branch pipe, 1m~2m away from the dehydrator.
5.1.4 The distance between the installation position of the water sealing of fire
barriering and explosion venting device and the farthest branch pipe (along the pipeline
axis) shall be less than 30m.
5.1.5 The water sealing of fire barriering and explosion venting device shall be able to
automatically control the water level. Make it maintain the effective fire-blocking water
seal height.
5.1.6 When the automatic explosion suppression device is selected as the explosion
suppression device, the distance between the installation position of the explosion
suppression device and the nearest flame sensor (along the axial direction of the
pipeline) is 40m~50m. When using explosion suppression devices for water mist
transportation or explosion suppression devices for two-phase-flow (gas-water), the
distance between the installation starting end and the water sealing of fire barriering and
explosion venting device shall not be greater than 3m.
5.1.7 The distance between the automatic preventing explosion device and the end of
the explosion suppressor of the explosion suppression device shall not be greater than
10m.
5.1.8 When the operating parameters of any device in the security facility cannot meet
the security requirements, it shall be able to realize automatic alarm. Then open the
drainpipe. Shut down the generator set within 3min after the alarm.
5.1.9 The nominal inner diameter of the pipeline in the installation section of the
security facilities shall meet the inner diameter requirements specified by the security
facilities and equipment.
5.2 Pipeline transportation for surface gas drainage
5.2.2 The flame sensor of the automatic explosion suppression device is installed on the
exhaust pipe. The distance from the outlet of the exhaust pipe (along the axial direction
of the pipe) shall be less than 5m.
5.2.3 The distance between the installation position of the explosion suppressor of the
automatic explosion suppression device and the flame sensor (along the axial direction
of the pipeline) is 30m~60m.
5.3 Pipeline transportation for low concentration gas in goaf drainage
5.3.1 For low concentration gas drainage in underground mined-out areas of coal seams
that are prone to spontaneous combustion and spontaneous combustion, explosion
suppression devices sha...
Get QUOTATION in 1-minute: Click GB 40881-2021
Historical versions: GB 40881-2021
Preview True-PDF (Reload/Scroll if blank)
GB 40881-2021: Code for security system design of low concentration gas pipeline transportation of coal mine
GB 40881-2021
GB
NATIONAL STANDARD OF THE
PEOPLE’S REPUBLIC OF CHINA
ICS 13.100
CCS D 09
Code for security system design of low concentration gas
pipeline transportation of coal mine
ISSUED ON: OCTOBER 11, 2021
IMPLEMENTED ON: MAY 01, 2022
Issued by: State Administration for Market Regulation;
Standardization Administration of the People's Republic of China.
Table of Contents
Foreword ... 3
Introduction ... 4
1 Scope ... 6
2 Normative references ... 6
3 Terms and definitions ... 7
4 Basic requirements ... 8
5 Security facilities ... 9
6 Others ... 12
Code for security system design of low concentration gas
pipeline transportation of coal mine
1 Scope
This document specifies the basic requirements for the design of the security system for
low concentration gas pipeline transportation of coal mine, the installation requirements
for security facilities.
This document is applicable to the security system design of low concentration gas
pipeline transportation of coal mine.
2 Normative references
The following referenced documents are indispensable for the application of this
document. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
GB 50016, Code for Fire Protection Design of Buildings
GB 50028, Code for design of city gas engineering
GB 50057, Code for design protection of structures against lightning
GB 50471, Code for design of the gas drainage engineering of coal mine
AQ 1072, Specification for water sealing of fire barriering and explosion venting
devices of gas pipeline transportation
AQ 1073, Specification for automatic preventing explosion devices of gas piping
AQ 1078, General specifications for transmission system of low concentration coal
mine gas blending with water mist
AQ 1079, General specification for automatic spurting powder explosion
suppression devices of gas pipeline transmission
AQ/T 1104, Technical Rules for the Security Delivery Device of Gas-water Two-
phase Flow of Low Concentration Gas in Coal Mine
CJJ 33, Code for construction and acceptance of city and town gas distribution
works
A device that the continuous mixing of gas and fine water mist in the coal mine gas
pipeline can inhibit the flame propagation of combustion or explosion.
4 Basic requirements
4.1 In the low concentration gas pipeline transportation of coal mine, close to the
possible fire source points (generator set intake side, ground emptying nozzle,
spontaneous combustion and easy spontaneous combustion coal seam gob drainage gas
pipe inlet), a security system shall be installed to ensure the security of pipeline
transportation.
4.2 The system design shall follow the basic principles of "fire and explosion prevention,
explosion suppression and explosion prevention, multi-level protection, and security
assurance". The security system shall choose different combinations of security
facilities such as fire and explosion relief, explosion suppression, explosion prevention,
anti-backflow, security monitoring and control, and lightning protection according to
the different uses of gas transportation.
4.3 Anti-backflow devices shall be installed in the positive pressure pipeline system.
Prevent backflow due to sudden shutdown of the extraction pump.
4.4 Buffer tanks shall not be installed in low concentration gas pipeline transportation
systems.
4.5 Pressurization equipment shall choose a wet compressor.
4.6 Drainage equipment shall choose wet drainage pumps.
4.7 When conveying under positive pressure, the conveying pressure shall not exceed
20kPa.
4.8 There shall be no mechanical moving parts and electrical components in the
dehydrator.
4.9 Security monitoring and control facilities shall be set up in the pipeline
transportation system. In addition to complying with the relevant provisions of MT209,
security monitoring and control facilities shall also have the following functions:
a) The function of state parameter monitoring and alarm of gas pipeline
transportation security facilities;
b) In the event of gas combustion or explosion, it shall be possible to control the
rapid start-up of security equipment. Control gas combustion or explosion within a
certain range.
4.10 The pipelines and accessories in the security facility installation section shall be
6 - Water sealing of fire barriering and explosion venting device;
7 - Pressure sensor;
8 - Flame sensor;
9 - Power equipment;
10 - Branch pipe;
11 - Airflow direction.
Figure 1 -- Schematic diagram of installation of security facilities for gas power
generation utilization system
5.1.3 Flame and pressure sensors for monitoring are installed on the branch pipe. The
flame sensor is no more than 3m away from the generator set. The pressure sensor is
3m~5m away from the flame sensor. If a dehydrator is installed on the branch pipe, the
flame sensor is located between the dehydrator and the generator set, 2m~3m away
from the dehydrator. The pressure sensor is located between the dehydrator and the
branch pipe, 1m~2m away from the dehydrator.
5.1.4 The distance between the installation position of the water sealing of fire
barriering and explosion venting device and the farthest branch pipe (along the pipeline
axis) shall be less than 30m.
5.1.5 The water sealing of fire barriering and explosion venting device shall be able to
automatically control the water level. Make it maintain the effective fire-blocking water
seal height.
5.1.6 When the automatic explosion suppression device is selected as the explosion
suppression device, the distance between the installation position of the explosion
suppression device and the nearest flame sensor (along the axial direction of the
pipeline) is 40m~50m. When using explosion suppression devices for water mist
transportation or explosion suppression devices for two-phase-flow (gas-water), the
distance between the installation starting end and the water sealing of fire barriering and
explosion venting device shall not be greater than 3m.
5.1.7 The distance between the automatic preventing explosion device and the end of
the explosion suppressor of the explosion suppression device shall not be greater than
10m.
5.1.8 When the operating parameters of any device in the security facility cannot meet
the security requirements, it shall be able to realize automatic alarm. Then open the
drainpipe. Shut down the generator set within 3min after the alarm.
5.1.9 The nominal inner diameter of the pipeline in the installation section of the
security facilities shall meet the inner diameter requirements specified by the security
facilities and equipment.
5.2 Pipeline transportation for surface gas drainage
5.2.2 The flame sensor of the automatic explosion suppression device is installed on the
exhaust pipe. The distance from the outlet of the exhaust pipe (along the axial direction
of the pipe) shall be less than 5m.
5.2.3 The distance between the installation position of the explosion suppressor of the
automatic explosion suppression device and the flame sensor (along the axial direction
of the pipeline) is 30m~60m.
5.3 Pipeline transportation for low concentration gas in goaf drainage
5.3.1 For low concentration gas drainage in underground mined-out areas of coal seams
that are prone to spontaneous combustion and spontaneous combustion, explosion
suppression devices sha...